2171 West Park Court, Suite # G, Stone Mountain, GA
|
|
|
|
|
Motion Control
Standard
Specifications
Power
|
380~460
VAC, 3-Phase, 3-Wire,
50/ 60 Hz
|
Tolerance
|
Voltage
tolerance: +10, -15%,
Frequency tolerance:
+/-5%
|
AXPERT
Eazy AMT- HF
|
1P5
|
2P2
|
4P0
|
5P5
|
7P5
|
011
|
015
|
018
|
022
|
030
|
037
|
Rated
Capacity
|
kW
|
1.5
|
2.2
|
4.0
|
5.5
|
7.5
|
11
|
15
|
18
|
22
|
30
|
37
|
Hp
|
2.0
|
3.0
|
5.0
|
7.5
|
10
|
15
|
20
|
25
|
30
|
40
|
50
|
Rated
Current (A)
Note 1
|
3.6
|
5.5
|
8.6
|
13
|
17
|
23
|
31
|
37
|
44
|
60
|
73
|
Applicable
Motor kW
|
1.5
|
2.2
|
4.0
|
5.5
|
7.5
|
11
|
15
|
18
|
22
|
30
|
37
|
Control
Functions
|
Control
Method
|
Space
Vector PWM Control
|
Frequency
Range
|
0.1~1800.0
Hz Constant or Variable
Torque
|
Output
Frequency Resolution
|
0.1
Hz (Digital), Max
Frequency/ 4096 (Analog)
|
Output
Frequency Stability
|
0.01%
(0~45 ºC)
|
V/
Hz Characteristics
|
2-Preprogrammed
patterns, 1-Custom
3-point setting pattern
|
Voltage
Boost
|
0~20%
|
Acceleration/
Deceleration Time
|
0.1~1200
Seconds (2 Ranges)
|
Linear
or S-Curve selective
|
Skip
Frequency
|
Three
frequencies can be set,
band can be set up to
10.0 Hz
|
Slip
Compensation
|
Slip
compensation frequency
up to 5.0 Hz
|
Carrier
Frequency
|
Default
10 kHz, 2.0 ~ 18.0 kHz
selectable with 0.1 kHz
resolution Note
2
|
Overload
Capacity
|
105%
continuous, 150%
Overload for 60 seconds
at every 10 minutes
|
Operation
Specifications
|
Speed
Search Function
|
When
enabled, rotating motor
can be started at any
moment
|
Power
Loss Carry Through
|
Up
to 5 seconds for smooth
operation of the system
during power loss
|
DC
Braking
|
DC
Braking start frequency
0.1~50 Hz, Time: 0~25
seconds, Brake current:
15 to 150%
|
Frequency
Setting Input
|
Digital
Input: Digital Operation
Panel (Local) or Serial
RS 485
|
Potentiometer:
2 k Ohm
|
FSV:
0~5Vdc or 0~10Vdc (or
Inverse)
|
FSI:
0~20mA or 4~20mA (or
Inverse)
|
VIN:
0~10Vdc
|
IIN:
4~20mA
|
Static
Pot: Freq
Increase/Frequency
Decrease using digital
I/P
|
Preset
Speeds: Using Preset
input-0, 1 & 2
|
Programmable
Analog Inputs
|
VIN:
0~10Vdc (or Inverse)
|
IIN:
4~20mA (or Inverse)
|
Input
Commands
|
Run,
Stop, Reverse, Jog,
Preset input-0, 1 &
2, Frequency Increase/
Frequency Decrease for
static potentiometer,
Run command with
maintained / momentary
facility, Ramp select,
Multi-motor selection
(Motor-1 ~ 15),
Emergency stop, Fault
reset, Ext Fault,
Terminal select, Ref
select 0 & 1.
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
Operation
Specifications
|
Speed
Search Function
|
2-Fixed
inputs for Run and Stop,
6-Programmable Sequence
Inputs, Sink / Source
changeable
|
|
Programmable
to 20 different options:
Not Used, Jog Select,
Ramp Select, Preset i/p-0,
Preset i/p-1, Preset i/p-2,
Freq Increase, Freq
Decrease, Emergency
Stop, Fault Reset, Ext
Fault, Terminal, Ref
Select 0, Ref Select 1,
Reverse, Base Ld I/P,
Motor Sel 1, Motor Sel
2, Motor Sel 3, Motor
Sel 4
|
Digital
outputs
|
4-Programmable
Sequence Outputs, open
collector type
|
|
Programmable
to 23 different options:
Not Used, Run, Local,
Reverse Run,
I-Detection, Freq
Attain, Speed Detect 1,
Speed Detect 2,
Acceleration,
Deceleration, Timer
Output, Zero Speed,
Fault Alarm, PID Up
Limit, PID Low Limit,
Gap Eliminator
Detection, Motor Sel 1,
Motor Sel 2, Motor Sel
3, Motor Sel 4, Thermal
Trip, Temp Alarm, Ready
|
Potential
Free Contacts
|
2-Programmable
relays
|
1-NO,
1-NC for 2A @ 240Vac
|
Programmable
to 23 different options
same as digital outputs
|
1-Fault
relay: 1-NO, 1-NC for 2A
@ 240Vac
|
Programmable
Analog Outputs
|
2-Programmable
analog voltage outputs
VO1 & VO2: 0~10Vdc
|
2-Programmable
analog current outputs
IO1 & IO2: 4~20mA
|
Programmable
between 7 different
options: Output
Frequency, Output
Current, Output Power,
Output Voltage, DC Bus
Volt, PID Output and
heatsink temperature
|
Network
connectivity
|
RS-485
for PC Interface with
Modbus-RTU protocol as
standard
|
Auto
Restart
|
Adjustable
up to 5 times for ten
faults
|
PID
Controller
|
Inbuilt
PID can be used as stand
alone
|
Display
|
Display
and Keypad unit
|
20-Character,
4-Line LCD panel with
backlit, 8-Key keypad,
3-Status indicating LED
for Run, Stop and Fault
-Simultaneous
display of eight
selectable monitor
parameters
|
Protective
Specifications
|
Protective
Function
|
Current
Limit, Over current
fault, Timed over
current fault, Load side
short circuit fault,
Under current fault,
Over voltage fault,
Under voltage fault,
Temperature fault,
Output phase loss fault,
Ground fault, External
fault, Charging fault,
Current sensor fail
fault, EEPROM Fault,
4~20 mA reference
missing fault, Emergency
stop, Communication loss
fault.
|
Smooth
Operation
|
Speed
Search, Auto Restart and
Power Loss Carry Through
functions
|
Fault
history
|
Last
ten faults with status
and operational
parameters like output
frequency, output
current, dc bus voltage
and heat sink
temperature.
|
Electronic
thermal overload
|
150%
Overload for 60 Seconds
|
Environment
|
Installation
location
|
Indoor
|
Ambient
temperature
|
0~50°C
(32~122°F)
|
Storage
temperature
|
-20~70°C
(-4~158°F)
|
Altitude
(above sea level)
|
3300ft
(1000 meter) without
derating, above 3300ft
(1000 meter) derate 5%
per 1000ft (305 meter)
|
Humidity
|
0~95%
maximum non-condensing
|
Enclosure
|
IP00
|
Note1:
Indicates the total effective
value including the higher
harmonics
Note2:
If the default carrier frequency
is exceeded, derate the output
current by 5% per 1kHz as the
reduced rating.
|
|
| |
|
|
|
|
|