Standard Specifications 

Power

380~460 VAC, 3-Phase, 3-Wire, 50/ 60 Hz

Tolerance 

Voltage tolerance: +10, -15%, Frequency tolerance: +/-5%

AXPERT Eazy AMT- HF

1P5

2P2

4P0

5P5

7P5

011

015

018

022

030

037

Rated Capacity

kW

1.5

2.2

4.0

5.5

7.5

11

15

18

22

30

37

Hp

2.0

3.0

5.0

7.5

10

15

20

25

30

40

50

Rated Current (A) Note 1

3.6

5.5

8.6

13

17

23

31

37

44

60

73

Applicable Motor kW

1.5

2.2

4.0

5.5

7.5

11

15

18

22

30

37

Control Functions

Control Method

Space Vector PWM Control

Frequency Range

0.1~1800.0 Hz Constant or Variable Torque

Output Frequency Resolution

0.1 Hz (Digital), Max Frequency/ 4096 (Analog)

Output Frequency Stability

0.01% (0~45 ºC)

V/ Hz Characteristics

2-Preprogrammed patterns, 1-Custom 3-point setting pattern

Voltage Boost

0~20%

Acceleration/ Deceleration Time

0.1~1200 Seconds (2 Ranges)

Linear or S-Curve selective

Skip Frequency

Three frequencies can be set, band can be set up to 10.0 Hz

Slip Compensation

Slip compensation frequency up to 5.0 Hz

Carrier Frequency

Default 10 kHz, 2.0 ~ 18.0 kHz selectable with 0.1 kHz resolution Note 2

Overload Capacity

105% continuous, 150% Overload for 60 seconds at every 10 minutes

Operation Specifications

Speed Search Function

When enabled, rotating motor can be started at any moment

Power Loss Carry Through

Up to 5 seconds for smooth operation of the system during power loss

DC Braking

DC Braking start frequency 0.1~50 Hz, Time: 0~25 seconds, Brake current: 15 to 150%

Frequency Setting Input

Digital Input: Digital Operation Panel (Local) or Serial RS 485

Potentiometer: 2 k Ohm

FSV: 0~5Vdc or 0~10Vdc (or Inverse)

FSI: 0~20mA or 4~20mA (or Inverse)

VIN: 0~10Vdc

IIN: 4~20mA

Static Pot: Freq Increase/Frequency Decrease using digital I/P

Preset Speeds: Using Preset input-0, 1 & 2

Programmable Analog Inputs

VIN: 0~10Vdc (or Inverse)

IIN: 4~20mA (or Inverse)

Input Commands

Run, Stop, Reverse, Jog, Preset input-0, 1 & 2, Frequency Increase/ Frequency Decrease for static potentiometer, Run command with maintained / momentary facility, Ramp select, Multi-motor selection (Motor-1 ~ 15), Emergency stop, Fault reset, Ext Fault, Terminal select, Ref select 0 & 1.

                           

 

Operation Specifications

Speed Search Function

2-Fixed inputs for Run and Stop, 6-Programmable Sequence Inputs, Sink / Source changeable