Power
|
380~460
VAC, 3-Phase, 3-Wire,
50/ 60 Hz
|
Tolerance
|
Voltage
tolerance: +10, -15%,
Frequency tolerance:
+/-5%
|
AXPERT
Eazy AMT- HF
|
1P5
|
2P2
|
4P0
|
5P5
|
7P5
|
011
|
015
|
018
|
022
|
030
|
037
|
Rated
Capacity
|
kW
|
1.5
|
2.2
|
4.0
|
5.5
|
7.5
|
11
|
15
|
18
|
22
|
30
|
37
|
Hp
|
2.0
|
3.0
|
5.0
|
7.5
|
10
|
15
|
20
|
25
|
30
|
40
|
50
|
Rated
Current (A)
Note 1
|
3.6
|
5.5
|
8.6
|
13
|
17
|
23
|
31
|
37
|
44
|
60
|
73
|
Applicable
Motor kW
|
1.5
|
2.2
|
4.0
|
5.5
|
7.5
|
11
|
15
|
18
|
22
|
30
|
37
|
Control
Functions
|
Control
Method
|
Space
Vector PWM Control
|
Frequency
Range
|
0.1~1800.0
Hz Constant or Variable
Torque
|
Output
Frequency Resolution
|
0.1
Hz (Digital), Max
Frequency/ 4096 (Analog)
|
Output
Frequency Stability
|
0.01%
(0~45 ºC)
|
V/
Hz Characteristics
|
2-Preprogrammed
patterns, 1-Custom
3-point setting pattern
|
Voltage
Boost
|
0~20%
|
Acceleration/
Deceleration Time
|
0.1~1200
Seconds (2 Ranges)
|
Linear
or S-Curve selective
|
Skip
Frequency
|
Three
frequencies can be set,
band can be set up to
10.0 Hz
|
Slip
Compensation
|
Slip
compensation frequency
up to 5.0 Hz
|
Carrier
Frequency
|
Default
10 kHz, 2.0 ~ 18.0 kHz
selectable with 0.1 kHz
resolution Note
2
|
Overload
Capacity
|
105%
continuous, 150%
Overload for 60 seconds
at every 10 minutes
|
Operation
Specifications
|
Speed
Search Function
|
When
enabled, rotating motor
can be started at any
moment
|
Power
Loss Carry Through
|
Up
to 5 seconds for smooth
operation of the system
during power loss
|
DC
Braking
|
DC
Braking start frequency
0.1~50 Hz, Time: 0~25
seconds, Brake current:
15 to 150%
|
Frequency
Setting Input
|
Digital
Input: Digital Operation
Panel (Local) or Serial
RS 485
|
Potentiometer:
2 k Ohm
|
FSV:
0~5Vdc or 0~10Vdc (or
Inverse)
|
FSI:
0~20mA or 4~20mA (or
Inverse)
|
VIN:
0~10Vdc
|
IIN:
4~20mA
|
Static
Pot: Freq
Increase/Frequency
Decrease using digital
I/P
|
Preset
Speeds: Using Preset
input-0, 1 & 2
|
Programmable
Analog Inputs
|
VIN:
0~10Vdc (or Inverse)
|
IIN:
4~20mA (or Inverse)
|
Input
Commands
|
Run,
Stop, Reverse, Jog,
Preset input-0, 1 &
2, Frequency Increase/
Frequency Decrease for
static potentiometer,
Run command with
maintained / momentary
facility, Ramp select,
Multi-motor selection
(Motor-1 ~ 15),
Emergency stop, Fault
reset, Ext Fault,
Terminal select, Ref
select 0 & 1.
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|