2171 West Park Court, Suite # G, Stone Mountain, GA
 FAQ

 

Motion Control

    MVD Specifications

                                                                  Click here for
                                                     | Product Description|Specification|


Drive Technology PWM-IGBT based design Digital
Input Voltage 3300V or 6000V ±10%, 3 Phase (Nominal)/13Kv
Input Frequency 50 Hz ±5%
Output Frequency Range 15-55Hz - Higher Frequency on request
Output Voltage 0 - Input Voltage
Speed Regulation Better than 1.0% With Slip Compensation
Efficiency Up to 95% on Rated Speed and Rated Load
Analog Input Speed Command 4-20mA or 0-10V dc or speed pot or RS485 set com pr keypad or digital
input
Hardware Digital Input/Output Input: Start, Stop, Local/Remote, Alarms/Faults, Jog, FWD, REV Output:
Ready, Run, Fault, Speed
Cooling Force Air Cooling
Communication RS485
Ambient Temperature -10º C- 50º C
Altitude 1000 Meters above sea level without derating
Relative Humidity 95% Non-Condensing
6 Pulse or 12 Pulse Rectifier is available to reduce the Harmonics
Additional I/O's Analogue digital on request